Support #580
Voltage protection: Undervoltage protection - 3ph operate
Added by Herbert Falk almost 4 years ago.
Updated over 1 year ago.
Category:
Standard extension required
Due date:
08/16/2021 (over 3 years late)
TF Unique ID:
52 # ENTSO-E
Discuss in Upcoming Meeting:
No
Short Proposal:
ENTSO-E to submit additional information.
Needs More Information:
No
Description
Voltage protection: Undervoltage protection - 3ph operate
Proposal descriptions
To be examined in 7-500 TF. (See #579)
- Category set to Standard extension required
- Status changed from New to In Progress
- Standard(s) set to IEC 61850-7-4, 7-5
- Discuss in Upcoming Meeting set to No
- Status changed from In Progress to Triage
- Short Proposal set to ENTSO-E to submit additional information.
- To discuss in WG10 set to No
ENTSO-E to submit additional information.
- Due date set to 08/16/2021
- Start date set to 02/16/2021
I think the requirement is to produce Op and Tr signals when there is an undervoltage on all 3 phases = an AND function.
As standard, the PTUV.Op is an OR function - at least one phase is under-voltage
Proposal : add a setting
NumPhsStr ENG Number of phases to start detection: values 1,2,3. If the DO is not present detection starts when one phase is undervoltage
See issue #579
- Status changed from Triage to Resolved
- Proposal descriptions updated (diff)
- Standard(s) changed from IEC 61850-7-4, 7-5 to IEC 61850-7-500
- Needs More Information set to No
- Copied to IEC61850-7-5 #6385: Voltage protection: Undervoltage protection - 3ph operate added
Also available in: Atom
PDF