Project

General

Profile

Bug #439

How to add utility process name to DOs

Added by Herbert Falk about 3 years ago. Updated 5 months ago.

Status:
Resolved
Priority:
High
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
2
Source:
Vattenfall
TF Unique ID:
2 # Vattenfall
WG10 Proposal:

19-01-23: Camille to distribute proposal for review (if accepted, will be implemented in next Revision/Ed)

Estimated Completion:
Ed 3
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

To use nsdoc files as holders of DO,DA standard descriptions (7-4, 7-3)If DO descriptions are to be changed, that should be done in SCL.

Standard(s):

IEC 61850-6

Needs More Information:
Yes
Assigned TF:

Description

Currently SCL has poor support for handling gateway/RTU-funktions where signal names are translated for remote communication. The specified sigal has a utility process name independent of used protcol. E.g. "start of distance protection". This needs to be associated with its IEC 61850 implementation (xxPDIS1.Str.general, xxPDIS2.Str.general etc.). The 80-1 part describes how 104 addresses can be added to SCL but also other utility fields are important to be able to include in SCL for specification and documentation purposes. Desired solution by Vattenfall is to have vendors use DA description to add utility process name.


Files

Vattenfall-Issue2-proposal_v3.docx Vattenfall-Issue2-proposal_v3.docx 15.8 KB Camille Bloch, 11/07/2023 08:33 AM

Related issues

Copied to IEC TC57 WG10 Future Work - WG10 Future Work #6579: How to add utility process name to DOsNew11/07/2023

Actions

Also available in: Atom PDF