470 IEC 61850 User Feedback Task Force Support 26 IOP_2013 Closed Normal An ICT provides an IID/ICD file that defines 4 GOCBs. The SCT imports this file, creates an SCD which has only 1 GOCB. The ICT r 06/21/2022 09:00 AM Actions
469 IEC 61850 User Feedback Task Force Support 25 IOP_2013 Closed Normal The iedType attribute is optional within SCL. However, some SCL tools use this as part of validation. Lack of the attribute/valu 06/21/2022 09:00 AM Actions
468 IEC 61850 User Feedback Task Force Support 24 IOP_2013 Closed Normal The mechanism for defining a GI attribute in a ED.2 RCB does not validate and import into an ED.1 ICT. 06/21/2022 09:00 AM Actions
467 IEC 61850 User Feedback Task Force Support 23 IOP_2013 Closed Normal There are normative ENUM definitions for 7-4. (e.g. Mod) but there is no guidance in regards to naming rules (e.g. Modkind). 06/21/2022 09:00 AM Actions
466 IEC 61850 User Feedback Task Force Support 22 (2) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. The question was if 06/21/2022 09:00 AM Actions
465 IEC 61850 User Feedback Task Force Support 22 (1) IOP_2013 Closed Normal In a SCD there were LNodes in the substation section that were not associated to a specific IED/LN instance. In particular, an S 06/21/2022 09:00 AM Actions
464 IEC 61850 User Feedback Task Force Support 21 IOP_2013 Closed Normal There is an issue about differentiation between “fixed” /preconfigured DataSets and those that can be changed in a SCT. Some ICT 06/21/2022 09:00 AM Actions
462 IEC 61850 User Feedback Task Force Support 19 IOP_2013 Closed Normal The use of ExtRef to subscribe to a SV was questioned. There are several different mechanisms that could be used in 61850-6 to s 06/21/2022 09:00 AM Actions
460 IEC 61850 User Feedback Task Force Support 17 IOP_2013 Closed Normal The usage of ClientLN in RptEna is optional. What does this mean. 61850-6 made this option for backward compatibility with ED.1. 06/21/2022 09:00 AM Actions
456 IEC 61850 User Feedback Task Force Support 13 IOP_2013 Closed Normal A client only ICD did not have a ClientServices section. An SCT imported the file and assigned used the IED to reserve a RCB wit 06/21/2022 09:00 AM Actions
455 IEC 61850 User Feedback Task Force Feature 12 IOP_2013 Closed Normal How does a SCT know the maximum number of instantiated RCBs allowed in an IED and what the allowed distribution per RCB? 02/11/2021 07:47 AM Actions
448 IEC 61850 User Feedback Task Force Feature 5 IOP_2013 Closed Normal ICD has a destination MAC address of 00:00:00:00:00. Is this valid for usage? 02/11/2021 07:50 AM Actions
518 IEC 61850 User Feedback Task Force Support 34 IOP_2015 Closed Normal Does the SVID character have to be specifically mentioned to be within 10-34 characters? Some of the vendors have implemented th 06/21/2022 09:12 AM Actions
517 IEC 61850 User Feedback Task Force Support 33 IOP_2015 Closed Normal IEC 61850-9-3 slaves can by design lock themselves to IEEE C37.238 (Power Profile) masters. This is intended behavior, since IEC 06/21/2022 09:12 AM Actions
516 IEC 61850 User Feedback Task Force Support 32 IOP_2015 Closed Normal Buffered reporting testing – anomaly with resynch (write of entryId failed, but buffered reports still sent). Because of indexe 06/21/2022 09:12 AM Actions
515 IEC 61850 User Feedback Task Force Support 31 IOP_2015 Closed Normal These test cases assume that a server will send a negative response to an operate to the same value. Some servers will accept th 06/21/2022 09:12 AM Actions
514 IEC 61850 User Feedback Task Force Support 29 IOP_2015 Closed Normal Priority of error checking in controls – i.e. position-reached instead of Blocked-by-switching-hierarchy. The order of checks i 06/21/2022 09:12 AM Actions
507 IEC 61850 User Feedback Task Force Support 22 IOP_2015 Closed Normal If the client reads a SCD file and loads then the data model (or vice versa ???) what data shall a client compare? confRef’s, da 06/21/2022 09:10 AM Actions
520 IEC 61850 User Feedback Task Force Support 1 IOP_2017/1 Closed Normal IEC 61850-6 leaves the definition of the meaning of the authentication options to the SCSM. However, neither 8-1 nor IEC 62351-6 06/21/2022 09:13 AM Actions
527 IEC 61850 User Feedback Task Force Support 8 IOP_2017/10 Closed Normal Regarding the Network infrastructure: Some MU/SAMU cannot configure their SV stream to different VLAN ID , fixed to 0 (but can c 06/21/2022 09:13 AM Actions
533 IEC 61850 User Feedback Task Force Support 14 IOP_2017/23 Closed Normal MSVID shall be unique. The integrated application SCD file allowed duplicate SVID’s for two merging units. 06/21/2022 09:13 AM Actions
536 IEC 61850 User Feedback Task Force Support 17 IOP_2017/26 Closed Normal SCT did not import GOOSE and 3 of the sampled value control blocks that existed in PMU ICD file. This caused validation failures 06/21/2022 09:13 AM Actions
599 IEC 61850 User Feedback Task Force Feature 12 IOP_2019 Resolved Normal ICD files do not match requirements (several issues) - increase in engineering efforts 06/05/2023 01:58 AM Actions
596 IEC 61850 User Feedback Task Force Feature 1710 IOP_2019 Closed Normal An IED declares constraints that are not machine processable 02/11/2021 06:43 AM Actions
592 IEC 61850 User Feedback Task Force Feature IntApp IOP_2019 Closed Normal Invalid SCL file due to wrong allocation fo GoCBs 06/21/2022 09:29 AM Actions