Project

General

Profile

Improvement #7095

DO "CECtl" and "Auto" of LN CCGR share a close semantic description

Added by Christophe Ghafari 14 days ago. Updated 8 days ago.

Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
01/08/2025
Due date:
% Done:

0%

Estimated time:
ID:
Source:
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
Yes
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4

Needs More Information:
No
Assigned TF:
61850-90-14 FACTS, HVDC & Powerconversion

Description

In IEC 61850-7-4, the LN CCGR contains 2 DO called "CECtl" and "Auto" (CDC SPC) sharing a close semantic description :
- CECtl : "(controllable) If true, automatic control of complete cooling group (pumps and fans) has been enabled, otherwise the control has been switched back from automatic to manual."
- Auto (inherited from AutomaticControlLN) : "(controllable) If true, output circuit of the automatic controller has been enabled (control is automatic), otherwise control is manual."

Clarification is required.

#1

Updated by Carlos Rodriguez del Castillo 8 days ago

  • Discuss in Upcoming Meeting changed from No to Yes
#2

Updated by Carlos Rodriguez del Castillo 8 days ago

  • Category set to Standard clarification required
  • Status changed from New to In Progress
  • Assigned TF 61850-90-14 FACTS, HVDC & Powerconversion added
  • Assigned TF deleted (None)

We need an explanation from 90-14 of the difference between "CECtl" and "Auto" because the descriptions are quite similar.
We will contact "Gaurav ROY" to ask the question.