Project

General

Profile

IEC61850-7-5 #6725

Simultaneous change of InRef.setSrcRef and InRef.setSrcCB for dynamic commutation

Added by Vladan Cvejic 9 months ago. Updated 9 months ago.

Status:
In Progress
Priority:
Normal
Assignee:
Start date:
05/31/2022
Due date:
% Done:

0%

Source:
RTE
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-5, IEC 61850-7-500
Related TISSUE:

Description

A simple static communication description in SCD based on “Input/ExtRef” combined with later binding is not always sufficient for all applications. Indeed, one of the most important use cases is redundancy management. For example, it may be necessary for a protection function to switch the subscription between SV streams published by two redundant MU or between GOOSE streams published by two redundant SCU.
The associated configuration used by Rte is based on the DO “InRef”. This DO allows to point to different IEC 61850 addresses and also to manage the test streams. The dynamic change to another SV or GOOSE stream is based on updating the Data Attributes (DA) “setSrcCB” and “setSrcRef”.

1. It seems required to have the capability of changing simultaneously the DA setSrcRef / setSrcCB of an InRef DO.
If not, there is a risk that the application use the wrong input signal while setSrcRef has changed and setSrcCB has not, for instance.

2. It seems required to have the capability of changing simultaneously the DA setSrcRef / setSrcCB of multiple InRef DO of a same LD.
If not, there is a risk that the application use for instance an input signal on SAMU A, and other inputs signal from SAMU B, which is discrepant from a system perspective.


Files

Multiplexer.PNG View Multiplexer.PNG 15.9 KB Vladan Cvejic, 06/07/2022 09:23 AM

Related issues

Copied from IEC TC57 WG10 Future Work - WG10 Future Work #5934: Simultaneous change of InRef.setSrcRef and InRef.setSrcCB for dynamic commutationNew05/31/2022

Actions

Also available in: Atom PDF