Project

General

Profile

Bug #671

Complete XSD file adding CDC CGS

Added by Maud Merley almost 3 years ago. Updated over 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Solved / Missunderstanding
Start date:
05/17/2021
Due date:
11/17/2021
% Done:

100%

Estimated time:
ID:
45
Source:
RTE
TF Unique ID:
45 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

90-4 has been updated in order not to have more proprietary CDCs

Standard(s):

IEC 61850-90-4

Needs More Information:
Assigned TF:

Description

The IEC 61850-90-4 defines a new common data class "CGS", for DO GmClkSt (Grandmaster clock status, according to IEEE C37.238), used in LTPC.
Currently, this CDC "CGS" is not declared in the IEC 61850-6 XSD, that leads to errors when validating SCL files using this CDC.

Should it be possible to add CDC "CGS" to the ENUM tPredefinedCDCEnum in the SCL_Enums.xsd file?


Proposal descriptions

IEC 61850-90-4 has been revised with an Ed2:
IEC TR 61850-90-4:2020
There is no proprietary CDCs anymore.

Also available in: Atom PDF