Bug #671
Complete XSD file adding CDC CGS
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Solved / Missunderstanding
Start date:
05/17/2021
Due date:
11/17/2021
% Done:
100%
Estimated time:
ID:
45
Source:
RTE
TF Unique ID:
45 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
90-4 has been updated in order not to have more proprietary CDCs
Standard(s):
IEC 61850-90-4
Needs More Information:
Assigned TF:
Description
The IEC 61850-90-4 defines a new common data class "CGS", for DO GmClkSt (Grandmaster clock status, according to IEEE C37.238), used in LTPC.
Currently, this CDC "CGS" is not declared in the IEC 61850-6 XSD, that leads to errors when validating SCL files using this CDC.
Should it be possible to add CDC "CGS" to the ENUM tPredefinedCDCEnum in the SCL_Enums.xsd file?
Proposal descriptions
IEC 61850-90-4 has been revised with an Ed2:
IEC TR 61850-90-4:2020
There is no proprietary CDCs anymore.
Updated by Carlos Rodriguez del Castillo almost 4 years ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Carlos Rodriguez del Castillo over 3 years ago
- Due date set to 11/17/2021
- Category set to Solved / Missunderstanding
- Status changed from New to Closed
- % Done changed from 0 to 100
- ID set to 45
- Source set to RTE
- TF Unique ID set to RTE # 45
- Discuss in Upcoming Meeting changed from Yes to No
- Proposal descriptions updated (diff)
- Short Proposal set to 90-4 has been updated in order not to have more proprietary CDCs
- Standard(s) set to IEC 61850-90-4