Issues #6595
Configuration and datamodel test cases not applicable for test equipment
Due date:
11/28/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
The Ed2.1 conformance test includes test cases for SCL configuration, data modelling and ICT tool export/import. For devices intended as test equipment these test procedures are not relevant. Test equipment is typically designed to simulate other devices. As such it needs to import a third party SCL to simulate. Also the server MICS statement is different, the MICS should specify which CDC's the test equipment can simulate.
The proposal is to add a generic statement that for test equipment (PIXIT-As9=Y) the data modelling and SCL configuration test cases are not applicable. For example:
For test equipment the data modelling and SCL configuration test cases are not applicable.