Configuration and datamodel test cases not applicable for test equipment

Added by Richard Schimmel 8 months ago. Updated 5 months ago.

Status:
Closed
Priority:
High
Due date:
11/28/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

The Ed2.1 conformance test includes test cases for SCL configuration, data modelling and ICT tool export/import. For devices intended as test equipment these test procedures are not relevant. Test equipment is typically designed to simulate other devices. As such it needs to import a third party SCL to simulate. Also the server MICS statement is different, the MICS should specify which CDC's the test equipment can simulate.

The proposal is to add a generic statement that for test equipment (PIXIT-As9=Y) the data modelling and SCL configuration test cases are not applicable. For example:

For test equipment the data modelling and SCL configuration test cases are not applicable.

#1

Updated by Thierry Dufaure 8 months ago

Engineering of the test system should include an import an an SCD File most likely, to simulate existing MCAA telegram.
I am not sure if test equipment should be limited in supported CDCs.
A test equipment may include an object model - and will be therewith included in the SCD file as well. The MICS is a mirror of the object model.

#2

Updated by IEC 61850 TPWG 8 months ago

  • Due date set to 11/28/2023
  • Status changed from New to In Progress

Accepted.

Import of SCD file shall be tested.

#3

Updated by Richard Schimmel 8 months ago

Second proposal:

For test equipment the data modelling and SCL configuration test cases are not applicable. The test equipment shall be able to import an SCD file provided by the test lab.

#4

Updated by IEC 61850 TPWG 8 months ago

  • Status changed from In Progress to Resolved
  • Assignee set to Richard Schimmel
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

Richard to add statement to TP:

For test equipment the data modelling and SCL configuration test cases are not applicable. The test equipment shall be able to import an SCD file provided by the test lab.

#5

Updated by Richard Schimmel 5 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3