Issues #6471
Select.response+ (Tissue 1753)
Due date:
08/22/2023 (about 16 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
cSBOns10
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Files
Updated by IEC 61850 TPWG over 1 year ago
- Project changed from Server to Client
- Due date set to 08/08/2023
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Updated by Richard Schimmel over 1 year ago
- File Solution to redmine 6471 Select Response.docx Solution to redmine 6471 Select Response.docx added
- Subject changed from Select.response+ to Select.response+ (Tissue 1753)
- Initial Test Document set to Client Amd1 TP1.0
- Test Case ID set to cSBOns10
- 61850 Standard 8-1 added
The tissue specifies:
Client implementation conformant to this standard shall accept for backward compatibility reason ANY non-null value in particular
[CO_ CtrlObjectRef]$Oper
[CO_ CtrlObjectRef]$SBO
Richard:
- Part 8-1 Ed1 $20.4.2 states: the Select Response+ is a non-NULL value for the SBO attribute.
- Part 8-1 Ed2.1 $20.5.4 states: the Select Response+ is a non-NULL value for the SBO attribute. But table 96 states <CO_ CtrlObjectRef>
Update sSBOns10 to use: any value not matching <CO_ CtrlObjectRef> for example with tailing $SBO/$Oper