Project

General

Profile

Issues #6471

Select.response+ (Tissue 1753)

Added by IEC 61850 TPWG 10 months ago. Updated 8 months ago.

Status:
Resolved
Priority:
Normal
Due date:
08/22/2023 (about 8 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
cSBOns10
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Files

#1

Updated by IEC 61850 TPWG 9 months ago

  • Project changed from Server to Client
  • Due date set to 08/08/2023
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel
#2

Updated by IEC 61850 TPWG 9 months ago

  • Due date changed from 08/08/2023 to 08/22/2023
#3

Updated by Richard Schimmel 8 months ago

The tissue specifies:
Client implementation conformant to this standard shall accept for backward compatibility reason ANY non-null value in particular
[CO_ CtrlObjectRef]$Oper
[CO_ CtrlObjectRef]$SBO

Richard:
- Part 8-1 Ed1 $20.4.2 states: the Select Response+ is a non-NULL value for the SBO attribute.
- Part 8-1 Ed2.1 $20.5.4 states: the Select Response+ is a non-NULL value for the SBO attribute. But table 96 states <CO_ CtrlObjectRef>

Update sSBOns10 to use: any value not matching <CO_ CtrlObjectRef> for example with tailing $SBO/$Oper

#4

Updated by Joel Greene 8 months ago

  • Status changed from In Progress to Resolved

Accepted

Also available in: Atom PDF