Project

General

Profile

Issues #6465

The Ed2 GOOSE performance also apply for Ed2Amd1

Added by Richard Schimmel 10 months ago. Updated 9 months ago.

Status:
Resolved
Priority:
Normal
Due date:
08/08/2023 (about 9 months late)
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The IEC 61850-5 performance requirements in Ed2Amd1 did not change. P1=3ms, P2=10ms etc.
As such we can apply the Ed2 test procedures also for Ed2Amd1.

I propose to update the title from:
- Test procedures for GOOSE performance according to IEC 61850-5 and IEC 61850-10 Edition 2
into:
- Test procedures for GOOSE performance according to IEC 61850-5 and IEC 61850-10 Edition 2 and Edition 2 with Amendment 1

The certificate should refer to the Edition of the device under test:
- IEC 61850-5 Edition 2 Performance Class P1 (3ms)
or
- IEC 61850-5 Edition 2 with Amendment 1 Performance Class P1 (3ms)


Files

Also available in: Atom PDF