Project

General

Profile

Issues #645

A4.11a - Test procedures indicates that all sample rates & number of ASDUs variant shall be tested

Added by Thierry Dufaure almost 4 years ago. Updated about 3 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
9-2
Triggering Tissue:
Final Decision:
See attachment 20210601
Updated Test Document:
Test Case ID:
SV general
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

Testing sample rates and number of ASDUs variants test should be limited to the real variant aspects, not to the generic communication tests: sSvp8 to sSvp22.
Propose to reduce the test scope for the publisher and actually subscriber variance. There shall be 1 main variant for the whole set of tests, and secondary variant for reduced test scope.


Files

processBusConfigurations.docx processBusConfigurations.docx 15.3 KB draft for proposal Thierry Dufaure, 03/23/2021 09:46 AM
ProcessBusConfigurations.xlsx ProcessBusConfigurations.xlsx 12.2 KB Thierry Dufaure, 04/12/2021 01:28 AM
Solution for SV testing.docx Solution for SV testing.docx 163 KB Richard Schimmel, 05/19/2021 10:24 AM
Solution for SV testing_20210601.docx Solution for SV testing_20210601.docx 159 KB Richard Schimmel, 06/01/2021 08:37 AM

Also available in: Atom PDF