Project

General

Profile

IEC61850-7-5 #6376

LN PDIF – setting for nominal current

Added by Vladan Cvejic over 1 year ago. Updated 9 months ago.

Status:
New
Priority:
Normal
Assignee:
-
Start date:
03/28/2023
Due date:
% Done:

0%

Source:
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-5
Related TISSUE:

Description

LN PDIF contains DO LoSet and HiSet which represent Low (resp High) operate value setting [%] relative to the nominal current.
As the nominal current is not a setting in PDIF, how could a user set the value of the threshold for minimal (resp. maximal) differential current ?

In practice, the base current for PDIF is often the highest primary nominal current of the associated TC.


Files


Related issues

Copied from IEC 61850 User Feedback Task Force - Support #6303: LN PDIF – setting for nominal currentResolvedChristophe Ghafari03/28/2023