Project

General

Profile

Improvement #630

XCBR LN new DO to describe withdrawable circuit breaker

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Category:
Standard extension required
Start date:
12/17/2020
Due date:
06/17/2021 (over 2 years late)
% Done:

0%

Estimated time:
ID:
43
Source:
RTE
TF Unique ID:
43 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Will be addressed by 7-5/7-500 Task Force.

Standard(s):

IEC 61850-7-500

Needs More Information:
No
Assigned TF:

Description

Need new DO in LN XCBR to describe withdrawable circuit breaker.
The informations needed are : position disconnected, DJ disconnected, DJ plugged in, Dryer fault.
A backup solution is to use LN XSWI. XSWI.Pos indicates whether the withdrawable circuit breaker is connected or deconnected.
Needed for some PACS functions.


Proposal descriptions

To be discussed inside WG10, as today it could be done with XCBR+XSWI, but it is not really a disconnector.


Related issues

Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6375: XCBR LN new DO to describe withdrawable circuit breakerIn ProgressChristoph Brunner12/17/202006/17/2021

Actions

Also available in: Atom PDF