sSrv9, sSrv10: change Table 3 to Table D.1 reference
Due date:
03/21/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sSrv9, sSrv10, sSrv11
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
In sSrv9 "Semantic of measured value (MV, CMV, WYE, DEL, SEQ" we find the following references: "IEC 61850-7-3 Subclause 6.2, 6.3, 6.4, 6.5 and 7.4.2, Table 3"
Reference to IEC 61850-7-3 Table 3 "Attributes of ValWithTrans" does not make sense here.
In Part 7-3 Ed.2 there was a Table 3 "Relation of the detailed quality identifiers with invalid or questionable quality" which fits. This table is moved to IEC 61850-7-2 Ed.2.1 Table D.1.
Propose to update the reference.