Feature #6225
Parameters not available in standardized LN - SetPhsOrig
Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
11/24/2020
Due date:
05/24/2021 (over 3 years late)
% Done:
0%
Estimated time:
ID:
60
Source:
RTE
TF Unique ID:
60 # RTE
WG10 Proposal:
SetPhsOrig: Information should be taken from the source
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
We need a clearer use case for SetPhNum proposal, to understand the dynamic change of the setting
Standard(s):
IEC 61850-7-4
Needs More Information:
Yes
Assigned TF:
Description
SetPhsOrig: Indication of single phase or combined phase voltage (a, b, c, ab, bc, ca, a_b_c, ab_bc_ca).
Should be used in each specific LN related to voltage (PIOC, PTOC, PTOV, PIOV, FXOT, FXUT…).
[ New parametres need to be modelled since they are not available in standard LNs. This issue refer to SetPhsOrig parameters, as explained in the attached documents by RTE.]
Files
Proposal descriptions
Last WG10 comment: SetPhNum/SetPhsOrig: Information should be taken from the source, using the connection between the source and the target P-Logical Nodes
Related issues