Feature #6225
Parameters not available in standardized LN - SetPhsOrig
0%
SetPhsOrig: Information should be taken from the source
We need a clearer use case for SetPhNum proposal, to understand the dynamic change of the setting
IEC 61850-7-4
Description
SetPhsOrig: Indication of single phase or combined phase voltage (a, b, c, ab, bc, ca, a_b_c, ab_bc_ca).
Should be used in each specific LN related to voltage (PIOC, PTOC, PTOV, PIOV, FXOT, FXUT…).
[ New parametres need to be modelled since they are not available in standard LNs. This issue refer to SetPhsOrig parameters, as explained in the attached documents by RTE.]
Files
Proposal descriptions
Last WG10 comment: SetPhNum/SetPhsOrig: Information should be taken from the source, using the connection between the source and the target P-Logical Nodes
Related issues
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Copied from Feature #6216: Parameters not available in standardized LN - SetPhNum added
Updated by Vladan Cvejic over 1 year ago
It is concluded that issue has to be presented and discussed on next joint meeting of TC57 & TC38 & TC95 in Lyon (May 25th, 2023). Will be presented by Maud Merley.