Feature #621
New controllable DO in RREC to define the mode of the recloser of the circuit breaker
Added by Carlos Rodriguez del Castillo almost 4 years ago.
Updated over 3 years ago.
Category:
Standard extension required
Due date:
11/24/2020 (over 4 years late)
Discuss in Upcoming Meeting:
No
Short Proposal:
RTE demands a new controllable data object (not only enumerated value)
Description
Details: Need to have a new controlable DO (as "RecCycMod") to define the mode of the recloser of the circuit breaker, in LN RREC; and to add new value to enumeration LiveDeadModeKind
Mode of recloser should be : live line dead bus, live bus dead lineā¦
RTE uses a mode live -line / live bus which is not present in the enumeration.
- Tracker changed from Bug to Feature
- Due date set to 11/24/2020
- Status changed from New to Resolved
- Short Proposal set to To add a new enumerated value to LiveDeadModeKind
- WG10 Proposal set to Accepted to be included in next amendment of 7-4
Discussion during meeting 2020-11-24:
It is RSYN the place. Two points:
- To create a new controllable DO (equivalent to LivDeaMod ENG) or change LivDeaMod to ENC --> We have to handle inside WG10 to decide about the first issue
- To add a new enumerated value to LiveDeadModeKind --> Accepted to update in next amendment of 7-4
- Start date changed from 10/07/2020 to 10/23/2020
- Assignee set to Carlos Rodriguez del Castillo
- WG10 Proposal changed from Accepted to be included in next amendment of 7-4 to Accepted to be included in next amendment of 7-4 (2.2)
- Discuss in Upcoming Meeting changed from Yes to No
- To discuss in WG10 set to No
2021-03-02: Carlos will contact Dawidczak, Henry to register by himself in the system and Herb will give him the role of developer. After that, Carlos will assign this issue to him.
- Status changed from Resolved to In Progress
- Short Proposal changed from To add a new enumerated value to LiveDeadModeKind to RTE demands a new controllable data object (not only enumerated value)
- Standard(s) changed from IEC 61850-7-4 to IEC 61850-7-4/7-500
- WG10 Proposal deleted (
Accepted to be included in next amendment of 7-4 (2.2))
2021-05-11: To handle this issue in 7-500 together with #647 issue.
- Copied to IEC61850-7-5 #6384: New controllable DO in RREC to define the mode of the recloser of the circuit breaker added