Feature #6219
Parameters not available in standardized LN - VRtg, ARtg and HzRtg
0%
This information should be part of the source to guarantee consistency of information
IEC 61850-7-4
Description
New parametres need to be modelled since they are not available in standard LNs.
This issue refer to VRtg, ARtg and HzRtg parameters, as explained in the attached documents by RTE.
Files
Proposal descriptions
Last WG10 comment: VRtg – ARtg – HzRtg: Similar to the other ones, this information should be part of the source to guarantee consistency of information, rather than having the same setting in all of the P-logical node instances. The question is how to be able to get this information and how to be sure that the information is in the CID file of the IED that needs the information. Possibilities: ExtRef with Poll method