Feature #6217
Parameters not available in standardized LN - NamAccRtg
0%
Should be taken from the SCL file. This setting is part of the TCTR/TVTR
IEC 61850-7-4
Description
New parametres need to be modelled since they are not available in standard LNs.
This issue refer to NamAccRtg parameters, as explained in the attached documents by RTE.
Files
Proposal descriptions
Last WG10 comment: NamAccRtg: Should be taken from the SCL file. This setting is part of the TCTR/TVTR
Related issues
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Copied from Feature #6216: Parameters not available in standardized LN - SetPhNum added
Updated by Carlos Rodriguez del Castillo almost 2 years ago
WG10 comment:
NamAccRtg: Should be taken from the SCL file. This setting is part of the TCTR/TVTR.
RTE comment:
It is correct that this information should be taken from TCTR/TVTR. Nevertheless, this corresponds to a setting of certain protection function (in particular Line Differential Protection).
It is thus necessary to express this information as setting information associated to the LN and it should be done using the same DO.
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- Copied to Feature #6218: Parameters not available in standardized LN - PhyConnITF added
Updated by Carlos Rodriguez del Castillo almost 2 years ago
- ID changed from 19 to 52
- TF Unique ID changed from 19 # RTE to 52 # RTE
Updated by Vladan Cvejic over 1 year ago
It is concluded that issue has to be presented and discussed on next joint meeting of TC57 & TC38 & TC95 in Lyon (May 25th, 2023). Will be presented by Maud Merley.