Feature #621

New controllable DO in RREC to define the mode of the recloser of the circuit breaker

Added by Carlos Rodriguez del Castillo about 3 years ago. Updated almost 3 years ago.

Status:
In Progress
Priority:
Normal
Category:
Standard extension required
Start date:
10/23/2020
Due date:
11/24/2020 (over 3 years late)
% Done:

0%

Estimated time:
ID:
17
Source:
RTE
TF Unique ID:
17 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

RTE demands a new controllable data object (not only enumerated value)

Standard(s):

IEC 61850-7-4/7-500

Needs More Information:
Assigned TF:

Description

Details: Need to have a new controlable DO (as "RecCycMod") to define the mode of the recloser of the circuit breaker, in LN RREC; and to add new value to enumeration LiveDeadModeKind
Mode of recloser should be : live line dead bus, live bus dead lineā€¦
RTE uses a mode live -line / live bus which is not present in the enumeration.


Related issues

Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6384: New controllable DO in RREC to define the mode of the recloser of the circuit breakerNew10/23/202011/24/2020

Actions
#1

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Tracker changed from Bug to Feature
  • Due date set to 11/24/2020
  • Status changed from New to Resolved
  • Short Proposal set to To add a new enumerated value to LiveDeadModeKind
  • WG10 Proposal set to Accepted to be included in next amendment of 7-4

Discussion during meeting 2020-11-24:
It is RSYN the place. Two points:
- To create a new controllable DO (equivalent to LivDeaMod ENG) or change LivDeaMod to ENC --> We have to handle inside WG10 to decide about the first issue
- To add a new enumerated value to LiveDeadModeKind --> Accepted to update in next amendment of 7-4

#2

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Start date changed from 10/07/2020 to 10/23/2020
#3

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Assignee set to Carlos Rodriguez del Castillo
  • WG10 Proposal changed from Accepted to be included in next amendment of 7-4 to Accepted to be included in next amendment of 7-4 (2.2)
  • Discuss in Upcoming Meeting changed from Yes to No
  • To discuss in WG10 set to No

2021-03-02: Carlos will contact Dawidczak, Henry to register by himself in the system and Herb will give him the role of developer. After that, Carlos will assign this issue to him.

#4

Updated by Carlos Rodriguez del Castillo almost 3 years ago

  • Status changed from Resolved to In Progress
  • Short Proposal changed from To add a new enumerated value to LiveDeadModeKind to RTE demands a new controllable data object (not only enumerated value)
  • Standard(s) changed from IEC 61850-7-4 to IEC 61850-7-4/7-500
  • WG10 Proposal deleted (Accepted to be included in next amendment of 7-4 (2.2))

2021-05-11: To handle this issue in 7-500 together with #647 issue.

#5

Updated by Vladan Cvejic 10 months ago

  • Copied to IEC61850-7-5 #6384: New controllable DO in RREC to define the mode of the recloser of the circuit breaker added