Issues #6192
Polarity of neutral in WYE
Due date:
01/24/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
deprecate PIXIT svp12 - polarity is now defined.
verify that subscriber can understand SV polarity
sSvp8 must be updated
subscriber test to be added
Files
Updated by Herbert Falk almost 2 years ago
- Status changed from New to In Progress
- Assignee changed from Richard Schimmel to Thierry Dufaure
Need to remove the svp12 from the test and make the test mandatory if SV publications.
Test ssvp8 needs to be modified.
Updated by Herbert Falk almost 2 years ago
The TPWG decided that there is a need to test the publisher emitting the correct sign and that a subscriber has the ability to be configured to reverse the polarity.
Need at least 2 test cases 1 for the publisher and 1 for the subscriber.
Updated by Thierry Dufaure almost 2 years ago
See attached test description modification to respond to tissue 1730
Updated by IEC 61850 TPWG almost 2 years ago
- Due date changed from 01/10/2023 to 01/24/2023
- Assignee changed from Thierry Dufaure to Richard Schimmel
Proposal accepted.
TISSUE 1730 updated.
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3