Feature #591

A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s AP

Added by Herbert Falk almost 4 years ago. Updated over 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1857
Source:
IOP_2019
TF Unique ID:
1857 # IOP_2019
WG10 Proposal:

Clarification will be done through tissues of issues 1337 and 1800.See 1337 issue.

Estimated Completion:
2022
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

The above citations show a need for clarification of the standard. The first citation seems to suggest that a ConnectedAP is only applicable to a server. The second seems to suggest that AccessPoint addresses are required to be unique – preventing a client and server from sharing an IP address.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

A reservation could not be made via SCL for an IED’s report due to the lack of a ConnectedAP associated with the client’s AccessPoint.

The ICD file describes its client and server via independent AccessPoint definitions.

-6 Ed2 :
First paragraph after table 36
“Each connected access point optionally has one server-related address, and additional address
information for real time communication-related control blocks such as GSE control and SMV
control. If all three are missing, it describes only the Subnetwork connection topology, for
example for communication performance studies. For a complete SCD file, either the server
address or at least one control block address shall be specified.”

9.4.3 Address definition
Second paragraph:
“The access point address shall be filled with a unique value at least for server type access
points to get a complete SCD description.”