Issues #5914
Verify that LPHD.Sim is not affected by LLN0.Beh
Added by IEC 61850 TPWG over 2 years ago.
Updated 9 months ago.
Discuss in Upcoming Meeting:
No
Closed Reason:
Test Procedure Update
Description
LPHD has no Beh, and therefore the service parameter test cannot be considered in the processing of the control service to LPHD.Sim
Files
- Triggering Tissue set to https://iec61850.tissue-db.com/tissue/1819
- Due date set to 09/06/2022
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Verify that LLN0.Beh does not affect the response of command service to LPHD.Sim
Set LLN0.Beh of LD containing LPHD to test. Verify that operate command with Oper.Test = false to LPHD.Sim is successful.
Pls review attached proposal for sClt29
Wait for TISSUE 1819 resolution
- Due date changed from 09/06/2022 to 10/18/2022
- Due date changed from 10/18/2022 to 11/15/2022
- Status changed from In Progress to Resolved
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3