Project

General

Profile

Issues #5914

Verify that LPHD.Sim is not affected by LLN0.Beh

Added by IEC 61850 TPWG over 2 years ago. Updated 9 months ago.

Status:
Closed
Priority:
Normal
Due date:
11/15/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl29 new
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

LPHD has no Beh, and therefore the service parameter test cannot be considered in the processing of the control service to LPHD.Sim


Files

#1

Updated by Joel Greene over 2 years ago

  • Triggering Tissue set to https://iec61850.tissue-db.com/tissue/1819
#2

Updated by IEC 61850 TPWG over 2 years ago

  • Due date set to 09/06/2022
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Verify that LLN0.Beh does not affect the response of command service to LPHD.Sim

Set LLN0.Beh of LD containing LPHD to test. Verify that operate command with Oper.Test = false to LPHD.Sim is successful.

#3

Updated by Richard Schimmel over 2 years ago

Pls review attached proposal for sClt29

#4

Updated by IEC 61850 TPWG about 2 years ago

Wait for TISSUE 1819 resolution

#5

Updated by IEC 61850 TPWG about 2 years ago

  • Due date changed from 09/06/2022 to 10/18/2022
#6

Updated by IEC 61850 TPWG about 2 years ago

  • Due date changed from 10/18/2022 to 11/15/2022
#7

Updated by IEC 61850 TPWG almost 2 years ago

  • Status changed from In Progress to Resolved
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)
#8

Updated by Richard Schimmel 9 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3