Verify that LPHD.Sim is not affected by LLN0.Beh

Added by IEC 61850 TPWG 2 months ago. Updated about 1 month ago.

Status:
In Progress
Priority:
Normal
Due date:
09/06/2022 (23 days late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl29 new
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

LPHD has no Beh, and therefore the service parameter test cannot be considered in the processing of the control service to LPHD.Sim


Files

#1

Updated by Joel Greene 2 months ago

  • Triggering Tissue set to https://iec61850.tissue-db.com/tissue/1819
#2

Updated by IEC 61850 TPWG about 2 months ago

  • Due date set to 09/06/2022
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Verify that LLN0.Beh does not affect the response of command service to LPHD.Sim

Set LLN0.Beh of LD containing LPHD to test. Verify that operate command with Oper.Test = false to LPHD.Sim is successful.

#3

Updated by Richard Schimmel about 1 month ago

Pls review attached proposal for sClt29