Project

General

Profile

Issues #5912

sSrv6 checking the read-only part is always applicable

Added by Richard Schimmel over 1 year ago. Updated about 2 months ago.

Status:
Closed
Priority:
Normal
Due date:
09/20/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sSrv6
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

sSrv6 step 1 and 2 can always be executed. Step 3-4-5-6 only when an attribute is writable.

Propose to make sSrv6 mandatory and change the text before step 4 into "When write-enabled data-attributes are available perform for each type"


Files

Solution to redmine sSrv6 5912.docx Solution to redmine sSrv6 5912.docx 19.8 KB Richard Schimmel, 08/23/2022 10:02 AM
#1

Updated by IEC 61850 TPWG over 1 year ago

  • Due date set to 09/06/2022
  • Status changed from New to In Progress

make sSrv6 mandatory and change the text before step 4 into "When write-enabled data-attributes are available perform for each type"

#2

Updated by IEC 61850 TPWG over 1 year ago

  • Assignee set to Richard Schimmel
#3

Updated by Richard Schimmel over 1 year ago

Pls review attached proposal.

#4

Updated by IEC 61850 TPWG over 1 year ago

  • Due date changed from 09/06/2022 to 09/20/2022
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

We need to define the criteria for determining what is read only.

#5

Updated by Thierry Dufaure over 1 year ago

We need to define criteria for determining what is writable. Maybe we can get inspired from sSrvN2. FC=CF/DC/SP and valKind != Set or absent.

#6

Updated by Richard Schimmel over 1 year ago

sSrv6 expected result already specifies what valKind is read-only and writable:

2. DUT sends SetDataValues(FC=BL, CF, SP, DC) response- for read-only data and response+ for write enabled data as specified in the ICD using valKind=”RO” for read-only and valKind=“Set” or missing for write enabled data attributes.

#7

Updated by IEC 61850 TPWG over 1 year ago

  • Status changed from In Progress to Resolved
#8

Updated by Richard Schimmel about 2 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3

Also available in: Atom PDF