Feature #589

Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1700
Source:
IOP_2019
TF Unique ID:
1700 # IOP_2019
WG10 Proposal:

CBL to create a tissue to clarify usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled.Folder has been created, Camille Bloch to create the tissue (sep-20)

Estimated Completion:
Once the folder for edition 2.1 is created in the new tissue database. Around june-20
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Verify the conformance test and of ClientLN vs maxAdditional information: Server is using AA Specific and needs a mechanism to allow Clients to be notified that they need to pay attention to the control block.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

Under the report block (below), the device was not able to process the code with “indexed” = false and RptEnabled NOT EQUAL TO “1”. They had to change “indexed” to "true" if RptEnabled is GREATER THAN “1”.

<ReportControl desc="S" datSet="ds_rcb2" name="rcb4" intgPd="0" buffered="false" bufTime="0" confRev="10000" indexed="false" rptID="BT_BCUCCTBRK/LLN0.rcb4">
<TrgOps dchg="true" dupd="false" gi="true" period="false" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="false" reasonCode="false" seqNum="false" timeStamp="true"/>
<RptEnabled max="7">
From IEC61850-6 (2018), “indexed” must = true if the max number of enabled reports is greater than 1