Feature #589
Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled
0%
CBL to create a tissue to clarify usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled.Folder has been created, Camille Bloch to create the tissue (sep-20)
Verify the conformance test and of ClientLN vs maxAdditional information: Server is using AA Specific and needs a mechanism to allow Clients to be notified that they need to pay attention to the control block.
IEC 61850-6
Description
Under the report block (below), the device was not able to process the code with “indexed” = false and RptEnabled NOT EQUAL TO “1”. They had to change “indexed” to "true" if RptEnabled is GREATER THAN “1”.
<ReportControl desc="S" datSet="ds_rcb2" name="rcb4" intgPd="0" buffered="false" bufTime="0" confRev="10000" indexed="false" rptID="BT_BCUCCTBRK/LLN0.rcb4">
<TrgOps dchg="true" dupd="false" gi="true" period="false" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="false" reasonCode="false" seqNum="false" timeStamp="true"/>
<RptEnabled max="7">
From IEC61850-6 (2018), “indexed” must = true if the max number of enabled reports is greater than 1
Updated by Vladan Cvejic over 3 years ago
- Subject changed from Under the report block (below), the device was not able to process the code with “indexed” = false and RptEnabled NOT EQUAL TO “ to Usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled
- Status changed from New to In Progress
- Short Proposal changed from Verify the conformance test and of ClientLN vs max Additional information: Server is using AA Specific and needs a mechanism to allow Clients to be notified that they need to pay attention to the control block. to Verify the conformance test and of ClientLN vs maxAdditional information: Server is using AA Specific and needs a mechanism to allow Clients to be notified that they need to pay attention to the control block.
- Standard(s) changed from 6 to IEC 61850-6
- WG10 Proposal changed from CBL to create a tissue to clarify usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled. Folder has been created, Camille Bloch to create the tissue (sep-20) to CBL to create a tissue to clarify usage of max of RptEnabled when indexed attribute is false and the relationship to RptEnabled.Folder has been created, Camille Bloch to create the tissue (sep-20)
- Discuss in Upcoming Meeting set to No
Checking done.
Updated by Carlos Rodriguez del Castillo over 2 years ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Vladan Cvejic about 2 years ago
- Status changed from In Progress to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
- To discuss in WG10 set to No
Related TISSUE created #1771.