Project

General

Profile

Improvement #5876

Proposal of a new LN class ASWI

Added by Michael Haecker almost 2 years ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Category:
Requirement Spec of user
Start date:
07/01/2022
Due date:
12/31/2022 (about 16 months late)
% Done:

0%

Estimated time:
ID:
Source:
FNN Germany
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4 Ed.3

Needs More Information:
No
Assigned TF:

Description

This is to register a user requirement for a new LN class ASWI, independent from ASEQ LN class proposed in IEC/TR 61850-90-14 which is intended to model FACTS and HVDC Automatic Sequencer.

ASWI LN class should model an execution scheme of a series of switchgear controls. Once activated by a DOns control, it will go through a configured list of 1 … n individual switchgear controls (CSWI.Pos), with associated ctlVal for the intended switching directions, and will execute them one after the other. The successful execution of the actual step shall be the precondition for executing the next one.

Option: It should be possible to select the execution sequence (forward/backward) using the common ctlVal of the DOns control. In backward mode the ctlVal for the individual controls should be inverted.


Proposal descriptions

The proposal is to enhance the definiton of ASWI LN allowing multi equipment controlled by CSWI changind the presence condition of OpOpn, OpCls, SelOpn and SelCls data objects.
The work will be address in IEC 61850-7-4 Ed.3 as 90-6 TR LN definition is plan to be moved to this standard.


Related issues

Copied to IEC TC57 WG10 Future Work - WG10 Future Work #5933: Proposal of a new LN class ASWINew07/01/202212/31/2022

Actions
#1

Updated by Tetsuo Otani almost 2 years ago

ASWI has already been defined in IEC TR 61850-90-6. The functions identified here seems to be provided the ASWI in 90-6.

So please refer to it before you start to work on the LN design.

If the ASWI in 90-6 is not proper to implement the functions identified here, please define a logical node whose name is other than ASWI.

#2

Updated by Vladan Cvejic almost 2 years ago

  • Status changed from New to Triage
  • Discuss in Upcoming Meeting changed from Yes to No

To check in 90-6 if new requirements for ASWI are already met.

#3

Updated by Vladan Cvejic almost 2 years ago

  • Tracker changed from Support to Improvement
#4

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Discuss in Upcoming Meeting changed from No to Yes
#5

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Status changed from Triage to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
  • Proposal descriptions updated (diff)
  • Standard(s) set to IEC 61850-7-4 Ed.3

90-6 ASWI definition is only for a single equipment controlled by CSWI. It could be enhanced to admit at least one, but more than one, as it was done with GAPC in 90-11. In the context of 90-6 it could be restricted to only once.
In edition 3 there is a plan to move 90-6 TR LN definitions to IEC 61850-7-4, so this modification could be addressed then.

#6

Updated by Vladan Cvejic over 1 year ago

#7

Updated by Carlos Rodriguez del Castillo 12 months ago

  • Needs More Information set to No
#8

Updated by Carlos Rodriguez del Castillo 12 months ago

  • Discuss in Upcoming Meeting changed from No to Yes
#9

Updated by Carlos Rodriguez del Castillo 11 months ago

  • Discuss in Upcoming Meeting changed from Yes to No

Also available in: Atom PDF