Support #541
APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
22
Source:
IOP_2017/36
TF Unique ID:
22 # IOP_2017/36
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
Refer to WG10
Standard(s):
IEC 61850-9-2(LE), IEC 61869-9
Needs More Information:
Assigned TF:
Description
9-2 LE requires that the APPID shall always be 0X4000. In 61869-9 Table 908 it is recommended to be unique to allow for filtering and enforced by the configuration system. There should be a note to allow for backward compatibility for 9-2 LE systems.
Related issues