Project

General

Profile

Support #541

APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9

Added by Herbert Falk about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
22
Source:
IOP_2017/36
TF Unique ID:
22 # IOP_2017/36
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

Refer to WG10

Standard(s):

IEC 61850-9-2(LE), IEC 61869-9

Needs More Information:
Assigned TF:

Description

9-2 LE requires that the APPID shall always be 0X4000. In 61869-9 Table 908 it is recommended to be unique to allow for filtering and enforced by the configuration system. There should be a note to allow for backward compatibility for 9-2 LE systems.


Related issues

Related to IEC 61850 User Feedback Task Force - Support #632: APPID 0x4000 - Sampled ValuesResolved12/16/202006/16/2021

Actions
#1

Updated by Vladan Cvejic about 3 years ago

  • Subject changed from 9-2 LE requires that the APPID shall always be 0X4000. In 61869-9 Table 908 it is recommended to be unique to allow for filterin to APPID rules for backward compatible variants (9-2LE) shall be noted in IEC 61869-9
  • Category set to Standard clarification required
  • Status changed from New to In Progress
  • Standard(s) set to IEC 61850-9-2(LE), IEC 61869-9
  • Discuss in Upcoming Meeting set to No

Checking done.

#2

Updated by Carlos Rodriguez del Castillo about 3 years ago

  • Related to Support #632: APPID 0x4000 - Sampled Values added
#3

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Status changed from In Progress to Closed

Confirm to IEC 61850-6 editor that this issue has been accounted for.

Also available in: Atom PDF