Project

General

Profile

CIM Issues #5312

Change associations for meter UsagePoint to make it more like Measurements

Added by Tom Berry almost 3 years ago. Updated 11 months ago.

Status:
Review
Priority:
Normal
Author/Contact Info:
Base Release:
Solution to be Applied To:
Solution Version:
Solution Applied By:
Completion Date:
CIM Keywords:
Breaking Change:
Breaking Change Description:
CIM Impacted Groups:
WG13, WG14
Requestor:
Tom Berry
Standard(s):

IEC 61968

Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
02/09/2022
Origination ID:
Originally Assigned To:

Description

The underlying use case is to make it easier to run analyses that combine meter readings with network models

One metering device can provide energy, RMS and many other variables for single point in the network, or for containers like a substation.
The protocol could be IEC 61850 or COSEM or something else
There are two choices for mapping these variables
1. Via Measurement: Equipment and Terminal are explicitly defined
2. Via Metering Usage Point: Terminal is implied by associated Equipment
This unambiguous for an EnergyConnection = DER
But it is ambiguous for branch devices e.g. supplying a Campus; or summary metering e.g. for a substation

Proposal: use same associations as Measurement
Deprecate UsagePoint -> Equipment
Add UsagePoint -> PowerSystemResource
Add UsagePoint -> ACDCTerminal


Files


Decision

As presented and discussed 9-Feb in UCA joint meeting