CIM Issues #5304

Clarify description on TransformerEnd attributes

Added by Pat Brown almost 3 years ago. Updated about 1 year ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
Tom McDermott, Chuck Dubose
Base Release:
Solution to be Applied To:
CIM18v03
Solution Version:
CIM18v03
Solution Applied By:
Chavdar Ivanov
Completion Date:
02/11/2023
CIM Keywords:
61970-Wires
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Pat Brown
Standard(s):

61970-301, 61970-452, 61968-13

Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
Origination ID:
Originally Assigned To:

Description

The use and meaning of the TransformerEnd.grounded, .rground and .xground attributes is not clear.


Proposed Solution

Clarify the meaning and use of the 3 TransformerEnd attributes.
Summary:

.grounded should be true if grounded, whether solidy or not
.rground and .xground are required if .grounded is TRUE and not to be present if .grounded is FALSE


Decision

452 constraint C:452:SC:PowerTransformerEnd.grounded:grounding


Release Notes

The following changes are applied

- Changed the description of TransformerEnd.grounded to: Used only for Yn and Zn connections indicated by PowerTransformerEnd.connectionKind. If true, the neutral is grounded and attributes TransformerEnd.rground and TransformerEnd.xground are required. If false, the attributes TransformerEnd.rground and TransformerEnd.xground are not considered.
- Changed the description of TransformerEnd.rground to: Resistance part of neutral impedance. Zero indicates solidly grounded or grounded through a reactor.
- Changed the description of TransformerEnd.xground to: Reactance part of neutral impedance. Zero indicates solidly grounded or grounded through a reactor.

the template of 452 is updated - the 452 constraint C:452:SC:PowerTransformerEnd.grounded:grounding is deleted as the constraint is integrated in teh description. In the template of 452 there is an action item to update SHACL constraints.

#1

Updated by Eric Stephan almost 3 years ago

  • Description updated (diff)
#2

Updated by Eric Stephan about 2 years ago

  • Status changed from New to Open
#3

Updated by Eric Stephan about 2 years ago

  • Status changed from Open to In Progress
  • Solution to be Applied To changed from iec61970cim18v01_iec61968cim14v00_iec62325cim04v08_CIM101.0 to 61970cim18
  • Solution Version set to CIM18v03
  • Decision updated (diff)
  • Release Notes updated (diff)

Previously in Release Notes section:

Change description of .grounded

from: (for Yn and Zn connections) True if the neutral is solidly grounded.
to: (for Yn and Zn connections) True if the neutral is grounded.

Change description of .rground

from: (for Yn and Zn connections) Resistance part of neutral impedance where 'grounded' is true.
to: (for Yn and Zn connections) Resistance part of neutral impedance where 'grounded' is true. Zero indicates solidly grounded or grounded through a reactor. Required if grounded=TRUE. Attribute should not exist if grounded=FALSE.

Change description of .xground

from: (for Yn and Zn connections) Reactive part of neutral impedance where 'grounded' is true.
to: (for Yn and Zn connections) Reactive part of neutral impedance where 'grounded' is true. Zero indicates solidly grounded or grounded through a resistor. Required if grounded=TRUE. Attribute should not exist if grounded=FALSE.

#4

Updated by Chavdar Ivanov almost 2 years ago

  • Status changed from In Progress to Closed
  • Solution Applied By changed from Pat Brown to Chavdar Ivanov
  • Completion Date set to 02/11/2023
  • Release Notes updated (diff)
#5

Updated by Todd Viegut about 1 year ago

  • Solution to be Applied To changed from 61970cim18 to CIM18v03