Feature #5087
Clarifications on the local/remote concept 7/8
0%
IEC 61850-7-4 Ed2.1 ,7-5
Description
Add a statement in the description text of 'MltLev' that this setting effects all contained LN instances of that LD.
Is the dependency of 'MltLev' limited to contained LN instances of that LD or, in the case of nested LD, including also subordinate levels?
Related issues
Updated by Vladan Cvejic almost 3 years ago
- Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
Updated by Vladan Cvejic almost 3 years ago
- Status changed from In Progress to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
Updated by Tom Berry almost 3 years ago
Draft proposal
When there are nested logical devices, the control service checks for local/remote should be similar to the checks for Mod/Beh.
When a control request is received at a Logical Node, the checks should take into account the status of the Loc, LocSta, MltLev data objects of the logical node, and also the Loc, LocSta, MltLev data objects of the LLN0 for all containing logical devices.
In the case of different values, "Loc=true", "LocSta=true", "MltLev=False" are dominant.
Updated by Tom Berry almost 3 years ago
- Standard(s) changed from IEC 618507-4 Ed2.1 to IEC 61850-7-4 Ed2.1 ,7-5
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from Yes to No
Updated by Vladan Cvejic over 1 year ago
- Copied to IEC61850-7-5 #6393: Clarifications on the local/remote concept 7/8 added