GSE MaxTime and MinTime parameters are optional with no default value

Added by Herbert Falk about 3 years ago. Updated about 2 years ago.

Status:
Closed
Priority:
High
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
6
Source:
IOP_2013
TF Unique ID:
6 # IOP_2013
WG10 Proposal:

According to Cathedral City meeting (ref. to UFTF-CathedralMOM20160219) this issue is closed.

Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Suggest that WG10 defines default behavior if these values are missing or declare them as mandatory for ED.2.

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

An SCL file was attempted to be imported that had TMAX and TMIN missing. The expected behavior for this case is not specified. And the file import was rejected.
61850-6 defines TMAX and TMIN as optional in order to provide backward compatibility with ED.1 schema. However, in ED.2 the fact that these are needed to control the expected behavior creates a need to define the default behavior or to develop a ED.2 profile that can be applied in addition to the XSD for validation.
Submit the concept of profiling to WG10


Proposal descriptions

Solved in edition 2.1

Also available in: Atom PDF