https://redmine.ucaiug.org/https://redmine.ucaiug.org/favicon.ico?15861924492021-02-03T21:59:21ZUCAIug Issue Tracking SystemIEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=742021-02-03T21:59:21ZHerbert Falk
<ul><li><strong>Priority</strong> changed from <i>Normal</i> to <i>High</i></li></ul> IEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=1192021-02-11T12:28:18ZCarlos Rodriguez del Castillo
<ul><li><strong>Subject</strong> changed from <i>An SCL file was attempted to be imported that had TMAX and TMIN missing. The expected behavior for this case is not specified. A</i> to <i>GSE MaxTime and MinTime parameters are optional with no default value</i></li><li><strong>Status</strong> changed from <i>New</i> to <i>Feedback</i></li><li><strong>Standard(s)</strong> set to <i>IEC 61850-6</i></li><li><strong>Discuss in Upcoming Meeting</strong> set to <i>No</i></li></ul><p>Checking done.<br />Check if it is really solved because I do not see any solution in part 6 ed2 o 8-1</p> IEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=1212021-02-11T12:31:06ZCarlos Rodriguez del Castillo
<ul><li><strong>Discuss in Upcoming Meeting</strong> changed from <i>No</i> to <i>Yes</i></li></ul> IEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=2902021-02-16T09:57:42ZCarlos Rodriguez del Castillo
<ul><li><strong>Status</strong> changed from <i>Feedback</i> to <i>Triage</i></li></ul> IEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=33522021-09-28T13:06:38ZThierry Dufaurethierry.dufaure@siemens.com
<ul></ul><p>IEC 61850-8-1 Ed2.1 as specified that minTime and maxTime are mandatory for a fully configured GSEControl.<br />(Text below table 163).<br />As well it is stated that:<br />"Configuration compliant with previous version of the standard may not contained the configured elements scl.tGSE.MinTime and scl.tGSE.MaxTime. It is a local issue of the publisher to use default values in that case. "</p> IEC 61850 User Feedback Task Force - Bug #449: GSE MaxTime and MinTime parameters are optional with no default valuehttps://redmine.ucaiug.org/issues/449?journal_id=38012022-03-15T14:40:41ZCarlos Rodriguez del Castillo
<ul><li><strong>Status</strong> changed from <i>Triage</i> to <i>Closed</i></li><li><strong>Discuss in Upcoming Meeting</strong> changed from <i>Yes</i> to <i>No</i></li><li><strong>Proposal descriptions</strong> updated (<a title="View differences" href="/journals/3801/diff?detail_id=4901">diff</a>)</li><li><strong>To discuss in WG10</strong> set to <i>No</i></li></ul>