Issues #1793
sGos22 - comment does not match expected result
Status:
Closed
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
IEC 61850-7-1 Annex K2.17
61850 Standard:
7-1
Triggering Tissue:
Final Decision:
See attachement
Initial Test Document:
Updated Test Document:
Test Case ID:
sGos22
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
The expected result is that the DUT subscribed to not only the Ed2 SPS but also to the Future edition SPC stVal!
Update the last line in the comment to:
Configure DUT to subscribe to the normal Ed2 Ind1.ST.stVal and Ind2.ST.stVal as well as FutInd1.ST.stVal and FutInd2.ST.stVal