Project

General

Profile

Improvement #7198

SwgTmms description not meaningful

Added by Christophe Ghafari about 2 months ago. Updated about 2 months ago.

Status:
Resolved
Priority:
Normal
Category:
-
Start date:
05/05/2025
Due date:
% Done:

0%

Estimated time:
ID:
Source:
TF Unique ID:
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4

Needs More Information:
No
Assigned TF:
61850-7-4

Description

In LN RPSB, the semantic of "SwgTmms" does not properly reflect that this is a time window. There is a possible risk of confusion with "instant of power swing detection".


Proposal descriptions

It is proposed to change the description to "Power Swing detection time (time window)".

Also available in: Atom PDF