Description
PIXIT-Rp13 is consistently utilized across all referring test cases where the RCB is pre-assigned (ResvTms = -1), with the exception of sBrN10.
Since sBrN10 exclusively involves BRCBs that are not pre-assigned, referencing Rp13 appears inconsistent.
sBrN10 addresses the scenario where ResvTms > 0 and the association is lost. Therefore, the test procedure should be updated to account for this scenario within ID Rp13 or a new PIXIT ID should be created.
Alternatives to fix PIXIT:
- Rp13: Does the server accept any client to configure/enable an RCB with:
-BRCB.ResvTms = -1, or
-URCB.Resv = T, or
-BRCB.ResvTms > 0 AND loss of association?
- Create a new PIXIT ID entry and modify sBrN10 to reference it to