Issues #7131
Update sGop13 test case with PIXiT max attributes
Status:
Resolved
Priority:
Normal
Assignee:
-
Due date:
04/01/2025 (18 days late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sGop13
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sGop13 is to verify that the DUT can publish dataset with ConfDataSet.maxAttributes entries.
This test case is mandatory and introduced by tissue 719 and also the final decision is written in IEC 61850 Part 6 ED2.1.
I propose to delete this test case based on the following reasons:
- This test case is mandatory but the ConfDataSet.maxAttriburtes is optional.
- I think the test case go beyond what the tissue 719 and the standard requires.
The TISSUE 719 and the standard only says that maxAttributes is the maximum number of FCDA elements (data set entries) allowed in a data set.
It defines that DUT's dataset ability and also clarify that the value is for data set entry.
I can not find in standard where says that the DUT has to publish GOOSE with maximum entry dataset.
When the DUT can support big dataset, and this big dataset is configured into GOOSE, test case sGopN2 will make sure that DUT can not publish it.
at the same time, to check tissue 719 and the standard's requirement, maybe we can update test case sCnf5 and sDs1:
for sCnf5:
it can add a description to create a dataset with max data set entries if ConfDataSet.maxAttriburtes is present.
for sDs1:
before step 1, address that associate with server using local maximumal PDU size.
and in step 1, the client will requests GetLogicalNodeDirectory, GetDatasetDirectory and GetDatasetValues.