Project

General

Profile

Issues #6991

sCnf75 not all devices have control objects

Added by Richard Schimmel 2 months ago. Updated 21 days ago.

Status:
Resolved
Priority:
Normal
Due date:
10/29/2024 (35 days late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf75
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Change to conditional with condition:

Condition: when Operate is supported (PICS)

#1

Updated by IEC 61850 TPWG 2 months ago

  • Due date set to 10/29/2024
  • Assignee set to Richard Schimmel

Disagree to make this conditional. Test as written appears to be correct.

Adding " only {status-only} object will pass the test" would clarify the test case.

#2

Updated by Richard Schimmel 22 days ago

Solution (changes in bold):

Verify for each (instance of) DOType/DA[name=ctlModel] whose associated EnumType contains direct-with-normal-security has in the DOType a DA named “Oper”. If ctlModel has valKind=RO and valImport=missing/false then use the configured ctlModel value instead of EnumType.
Similar for sbo-with-normal-security, Oper, Cancel and SBO
Similar for direct-with-enhanced-security, Oper
Similar for sbo-with-enhanced-security, Oper, Cancel and SBOw
ctlModel=status-only has no requirements on Oper

#3

Updated by IEC 61850 TPWG 21 days ago

  • Status changed from New to Resolved

Accepted.

Also available in: Atom PDF