Issues #6990
sSvp9 step 4 PTP class not 6/7 with/without holdover time?
Description
IEEE 1588 defines clock class 6-7-52-187. When the master clock looses the GPS signal the master will continue. After a while the master clock will have clock class 7 and then 52 and then 187. When should the MU set the SmpSynch=1? Should it do immediately after clock 52 is received? May/Shall it wait it's own holdover time?
IEC 61869-9 is not that clear on this.
Proposal to add the holdover time:
4. Force the global PTP master to local (clockClass not 6 and not 7) by for example disconnecting the GPS antenna, then wait the holdover time (TVTR/TCTR.HoldTmms) plus 30 seconds
Updated by IEC 61850 TPWG about 2 months ago
- Due date set to 10/29/2024
- Assignee set to Richard Schimmel
Needs further review. TVTR/TCTR.HoldTmms applies when PTP messages are not available.
Updated by IEC 61850 TPWG 26 days ago
- Due date changed from 10/29/2024 to 11/12/2024
SEL to provide input. Thierry believes that the MU holdover is not of relevance as clock master is where the signal is lost.
Updated by IEC 61850 TPWG 12 days ago
- Due date changed from 11/12/2024 to 12/10/2024
Tissues needed against 9-3, 61869-9
For the moment, PIXIT to describe the conditions to cause device to change smpSync