sCtl14 in TP1.3 does not reflect the Issue #6214 resolution

Added by Erik San Telmo 2 months ago. Updated 24 days ago.

Status:
Resolved
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl14
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The script has removed PIXIT Ct16 but is not forcing the negative response in step 2.

Please change the step 2 from:
2. DUT responds as specified in PIXIT
to
2. DUT responds with Operate response- with AddCause = command-already-in-execution or AddCause = locked-by-other-client

Please, also remove the last sentece:
In case of Operate response- the AddCause = command-already-in-execution or AddCause = locked-by-other-client

Thank you.

#1

Updated by Richard Schimmel about 2 months ago

  • Status changed from New to In Progress
  • Initial Test Document set to TP1.3
  • Test Case ID set to sCtl14

Indeed sCtl14 need to be improved. PIXIT Ct30 is only about operate time and is not relevant for expected result step 2.

I agree with the above proposal:
2. DUT responds with Operate response- with AddCause = command-already-in-execution or AddCause = locked-by-other-client

#2

Updated by IEC 61850 TPWG 24 days ago

  • Status changed from In Progress to Resolved
  • Assignee set to Richard Schimmel

Accepted