IEC61850-7-5 #6787

Harmonization of Table 4 with Figure 22

Added by Michael Haecker about 1 month ago. Updated 10 days ago.

Status:
In Progress
Priority:
Normal
Start date:
05/15/2024
Due date:
% Done:

0%

Source:
Category:
Not yet categorized
TF 7-5 Project document:
IEC 61850-7-500
Related TISSUE:

Description

Table 4 shows a sequence where XCBR.Pos.opOk=FALSE occurs before XCBR.Pos [new] . This is not quite in line with the reality.
Figure 22 shows new Pos.stVal followed by exit/reset OpOk . This is correct.

In reality, the new position is observed by XCBR which will then both disable the output contact and reset 'OpOk' .

Propose to exchange the sequence of the two lines in Table 4 to state "exit/reset CSWI.OpOpn/Cls.general=FALSE GOOSE <-- XCBR.Pos [new]" before "exit/reset CSWI.Pos.opOk=FALSE GOOSE <-- XCBR.Pos.opOk=FALSE" .


Related issues

Related to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6698: Integrate work from AHTF Control Between FunctionsNew02/07/2024

Actions
#1

Updated by Keith Gray 17 days ago

Discussed during 2024/06/05 WG10 meeting in Marlboro:
  • Determined that the Table 4 is correct, the Figure 22 needs to change to match Table 4
#2

Updated by Keith Gray 10 days ago

Updated the document during the 2024/06/13 TF7-5/7-500 meeting.

We also noted that this table will change once the "Control Between Functions" task force work is implemented.

#3

Updated by Keith Gray 10 days ago

#4

Updated by Keith Gray 10 days ago

  • Status changed from New to In Progress