sCtl5 to be more precise related to "blocked" and "test/blocked"

Added by Michael Haecker over 3 years ago. Updated about 3 years ago.

Status:
Closed
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-4
Triggering Tissue:
Final Decision:
See last attachment
Updated Test Document:
Test Case ID:
sCtl5
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

For steps 6,7,8 and 9,10,11 some statements to be added.

The existing steps apply for implementations where the LN instance hosting the controllable object is wired to electrical periphery. For other schemes, new test cases are to be created, stating which LN.Beh is "blocked", "test/blocked" respectively. For implementations where the LN instance hosting the controllable object is separated from the proxy LN instance which is wired to electrical periphery (ex. CSWI, XCBR), the AddCause "time-limit-over" may be issued since the proxy LN instance did not execute the control command.

The expected results for
- step6 add: The AddCause "blocked-by-mode" shall be issued.
- step7 ok
- step8 Since Tissue #1769 "The value of the test flag in the control command for Mod (Mod.Operate.test attribute) shall be ignored." the test could be amended to "... Mod control command with and without test flag set"

- step9 ok
- step10 add: The AddCause "blocked-by-mode" shall be issued.
- step11 same remark as for step8

Since sCtl28 was modified to no more include testing of "blocked" and "test/blocked", sCtl5 remains the only TP to test them. sCtl5 headline to be modified to state "blocked" and "test/blocked".


Files


Related issues

Related to Server - Issues #668: MirrorBlockCommand state not used for LNs without direct process interface (sCtl28)ClosedRichard SchimmelActions

Also available in: Atom PDF