Issues #6688
cSrvN10 - Ed1 specific error codes do not exist for MMS GetNameList
Due date:
04/02/2024 (about 8 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
cSrvN10
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
Ed2.1 clients shall be backwards compatible with Ed1 devices. Ed1 allows for several MMS services specific error codes which are not-allowed anymore in Ed2. So it does make sense to test those Ed1 specific errors. However for MMS GetNameList Ed1 has the exact same error codes as in Ed2/Ed2.1. As such it's not possible to perform the test as described in cSrvN10. We could test all kind of error codes but there should be a good reason to do so. I don't see such reason for sSrvN10
My proposal is to deprecated cSrvN10 (and other GetNameList test cases requiring Ed1 specific error codes).
Related issues