Project

General

Profile

Improvement #667

Report of current active setting group

Added by Carlos Rodriguez del Castillo over 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
05/11/2021
Due date:
11/11/2021 (over 3 years late)
% Done:

0%

Estimated time:
ID:
4
Source:
WG10
TF Unique ID:
WG10 # 4
WG10 Proposal:
Estimated Completion:
IEC 61850-7-4 edition 3
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

To create a new INS data object in the LLN0 where SCGB is defined. A new presence condition is needed. To be included in IEC 61850-7-4 ed3.

Standard(s):

IEC 61850-7-4

Needs More Information:
No
Assigned TF:

Description

The current active setting group cannot be sent in a report in an spontaneous way, and you can only use GetDataValues (polling) service.
Today some users define a INS data object with the setting group number, others define several SPS objects to indicate which seeting group is active.


Proposal descriptions

Service tracking gives information about the current setting group, but it is not possible by GOOSE or report. If you want to raise an action on other device due to a setting group change, then you need a data object with TrgOpts d-chg in order to be able to do it.


Related issues

Copied to IEC TC57 WG10 Future Work - WG10 Future Work #5937: Report of current active setting groupNew05/11/2021

Actions

Also available in: Atom PDF