Project

General

Profile

Issues #6598

Using the same dataset in URCB, BRCB and GoCB

Added by Richard Schimmel 6 months ago. Updated about 2 months ago.

Status:
Closed
Priority:
Normal
Due date:
01/09/2024
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The standard has no restrictions about using the same dataset in URCB, BRCB and/or GoCB. In case an server or ICT does not allow this it may cause interoperability issues! I propose we update sCnf5 to verify the server devices/ICT tool do allow this.


Files

#1

Updated by IEC 61850 TPWG 5 months ago

  • Due date set to 12/12/2023
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Accepted.

#2

Updated by IEC 61850 TPWG 5 months ago

  • Due date changed from 12/12/2023 to 01/09/2024
#3

Updated by Richard Schimmel 4 months ago

Added solution

#5

Updated by IEC 61850 TPWG 4 months ago

  • Status changed from In Progress to Resolved
#6

Updated by Richard Schimmel about 2 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3

Also available in: Atom PDF