Issues #6591
sSg11 - Non-volatile property test (for various FCs)
Status:
Rejected
Priority:
Normal
Assignee:
-
Due date:
12/29/2023 (about 12 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Duplicate Issue
Triggering Tissue 2:
Triggering Tissue 3:
Description
In the test of sSg11, the Setting Group (FC=SP) has a non-volatile property that has the previous value even after restart.
On the other hand, other nonvolatile FCs such as CF, DC, and EX do not maintain their existing values before and after the restart and are initialized or have different values.
It seems necessary to test the non-volatile property for other FCs.
Related issues
Updated by Thierry Dufaure about 1 year ago
- Triggering Tissue set to https://iec61850.tissue-db.com/tissue/1822
This is also the conclusion of https://iec61850.tissue-db.com/tissue/1822
Updated by Richard Schimmel about 1 year ago
- Related to Issues #6564: Functional constraint object non-volatility ambiguous - 1822 added
Updated by IEC 61850 TPWG about 1 year ago
- Status changed from New to Rejected
- Closed Reason Duplicate Issue added
- Closed Reason deleted (
--Not Set---)