Issues #652
Publisher can use maximum number of dataset elements
Due date:
11/29/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
8-1
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sGop13
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
Item 2 from TF Christophe Camelis; Shall we add a test case or not?
Files
Related issues
Updated by Joel Greene over 2 years ago
- Subject changed from Publisher can use maximum number of minimum sized dataset elements to Publisher can use maximum number of dataset elements
- Due date set to 08/09/2022
- Status changed from New to In Progress
- Assignee set to Christophe CAMELIS
Some interpretation of maxAttributes is ambiguous. Clarified to mean ds members regardless of FCD or FCDA.
https://iec61850.tissue-db.com/tissue/719
ICTs and servers found to enforce wrong rule.
Test case makes sense.
Updated by Joel Greene over 2 years ago
- Related to Issues #655: Publish/subscribe maximum length data added
Updated by IEC 61850 TPWG over 2 years ago
- Due date changed from 08/09/2022 to 10/04/2022
- Assignee changed from Christophe CAMELIS to Richard Schimmel
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)
Updated by Richard Schimmel about 2 years ago
- File Solution to redmine 0652 sGop13 max dataset.docx Solution to redmine 0652 sGop13 max dataset.docx added
- Initial Test Document set to Amd1 TP1.2
- Test Case ID set to sGop13
Added attachment for sGop13
Updated by IEC 61850 TPWG about 2 years ago
- Due date changed from 10/04/2022 to 11/29/2022
- Status changed from In Progress to Resolved
Updated by Richard Schimmel 10 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3